Place of Origin: | Zhejiang, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
Easy Shipping and Assembling Mini 9 Cubic Walk-in Environmental Chamber
1. Safety Assurance:
Standard is a redundant control circuit with its own controller and failsafe contactor. To prevent thermal runaway, the safety control shuts off power to the heater circuit and the circulation blowers continue to distriibute heat within the room. This feature is particularly important if there are heat-generating items in the walk-in room. When the temperature goes down, the safety control closes and power is restored to the heaters.
1.1 Other available safety options are:
High Temperature Safety with Complete Shut Down of Room with Manual Reset and Visual Indication,
Low Temperature Safety with Complete Shut Down of Room with Manual Reset and Visual Indication,
Both High and Low Temperature Safety with Manual Reset on Both and Visual Indication, Audible Alarm, and Remote Station Alarms.
2. Instrumentation
Instrumentation consists of either single or two-channel microprocessor programmers with an accuracy of ±.25°C or better at the sensor. The sensors are fast acting 100 Ohm. platinum type.
Other options include: RS-232, RS-485 interface.
3. Explore Walk-In Rooms by KOMEG:
Associated Environmental Systems offers a range of prefabricated, tight-tolerance environmental walk-in rooms that are easy to ship and install. Major features include:
Forced air circulation systems distribute air evenly and constantly recirculate it, maintaining uniform and accurate temperatures and humidity.
Temperature Ranges are from -60°C (-140°F) to +120°C (458°F ).
Refrigeration system meets the room's load demand and operates continuously in cooling mode. Single-stage mechanical units operate at -35°C and above and two-stage cascade units at below -35°C.
Electric heating system provides very accurate and straight line control of temperatures. System is reliable and has a long life.
Humidity System choices are the conditioned fine Mist System or the Steam Generator System. Different ranges are available including special dehumidity ranges to 5% RH.
Prefabricated room construction consists of modular, sandwich-type panels with a metal skin inside and outside. Panels are easy to ship and assemble.
Multipane viewing windows can be ordered in custom sizes.
Incandescent or fluorescent lighting is vapor-proofed and sealed.
Instrumentation consists of single or two-channel microprocessor programmers with an accuracy of ±.25°C or better at the sensor. Other options include: RS-232C, RS-422A, IEEE-488 interface.
Safety standard is a redundant control circuit with its own controller and failsafe contactor. Many other options are available.
4. Main Technical Parameters
Model | KMHW-4 | |||||||
Volume(m³) | 9CBM | |||||||
Interior Dimensions | W2100 x H2100 x D2050mm | |||||||
Exterior Dimensions | W3250 x H2350 x D2250mm | |||||||
Safety Devices(standard) | No fuse breaker, over pressure, over heat and over current protection for compressor, over temperature protection, over load protection for blower, dry heat protection | |||||||
Standard accessories | Sight window*1, cable port ( portΦ50mm ) *1, chamber lamp*1, status indicator | |||||||
Control System | Balanced Temperature & Humidity Control System | |||||||
Refrigeration system | Water Cooled | |||||||
Semi-hermetic compressor, single stage or cascade refrigeration system, | ||||||||
CFC free refrigerant ( HFC-507 and HFC-23 ) | ||||||||