KOMEG Technology Ind Co., Limited
|
Place of Origin: | Zhejiang, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
Easy Ship and Assemble Mini Style 9 Cubic Environmental Walk-in Room
1. Explore Walk-In Rooms by KOMEG:
Associated Environmental Systems offers a range of prefabricated, tight-tolerance environmental walk-in rooms that are easy to ship and install. Major features include:
Forced air circulation systems distribute air evenly and constantly recirculate it, maintaining uniform and accurate temperatures and humidity.
Temperature Ranges are from -60°C (-140°F) to +120°C (458°F ).
Refrigeration system meets the room's load demand and operates continuously in cooling mode. Single-stage mechanical units operate at -35°C and above and two-stage cascade units at below -35°C.
Electric heating system provides very accurate and straight line control of temperatures. System is reliable and has a long life.
Humidity System choices are the conditioned fine Mist System or the Steam Generator System. Different ranges are available including special dehumidity ranges to 5% RH.
Prefabricated room construction consists of modular, sandwich-type panels with a metal skin inside and outside. Panels are easy to ship and assemble.
Multipane viewing windows can be ordered in custom sizes.
Incandescent or fluorescent lighting is vapor-proofed and sealed.
Instrumentation consists of single or two-channel microprocessor programmers with an accuracy of ±.25°C or better at the sensor. Other options include: RS-232C, RS-422A, IEEE-488 interface.
Safety standard is a redundant control circuit with its own controller and failsafe contactor. Many other options are available.
2. Main Technical Parameters
Model | KMHW-4 | |||||||
Volume(m³) | 9CBM | |||||||
Interior Dimensions | W2100 x H2100 x D2050mm | |||||||
Exterior Dimensions | W3250 x H2350 x D2250mm | |||||||
Safety Devices(standard) | No fuse breaker, over pressure, over heat and over current protection for compressor, over temperature protection, over load protection for blower, dry heat protection | |||||||
Standard accessories | Sight window*1, cable port ( portΦ50mm ) *1, chamber lamp*1, status indicator | |||||||
Control System | Balanced Temperature & Humidity Control System | |||||||
Refrigeration system | Water Cooled | |||||||
Semi-hermetic compressor, single stage or cascade refrigeration system, | ||||||||
CFC free refrigerant ( HFC-507 and HFC-23 ) | ||||||||
Controller | Panel | 7-inch LCD Touch panel, Chinese or English display selectable | ||||||
Operation model | Program or fix point running | |||||||
Memory capacity | 120 programs,1200steps, all repeat 999 cycles,part repeat 99 cycles | |||||||
Accuracy | Temp.:0.1% of F.S ± 1 digit Humidity:0.1% of F.S ± 1 digit | |||||||
Input | Temp.: pt-100, Humidity: pt-100 or 5V DCV | |||||||
Comm.port | RS-232 or RS-485 ( Softawre is option) | |||||||
Temp. range | Maximum: 80 ºC,120 ºC; Minimum: -60 ºC, -50 ºC, -40 ºC, -30 ºC, -20 ºC, -10 ºC, 0 ºC |
|||||||
Humidity Range | 10%, 20%, 30% ~ 95% | |||||||
Temp. constancy | ±0.5 ºC | |||||||
Humidity constancy | ±2.5%R.H | |||||||
Temp. uniformity | ±2.0 ºC | |||||||
Humidity uniformity | ±5.0%R.H | |||||||
Ambient Temp. | +5 ºC+35 ºC | |||||||
Wiring method | AC 380 ± 10% 50Hz ,3 phase 4 wires + Ground Wires | |||||||
Heat up time | +20 ºC+80 ºC, Within 60 min | |||||||
Pull down time | +20 ºC ~ -55 º, -40 ºC, -20 ºC, -10 ºC, Within 120 or 90 or 60 min | |||||||
Interior material | Stainless Steel Plate(SUS 304) | |||||||
Exterior material | Baked Painting Steel Or Stainless steel ( SUS304) | |||||||
Insulation material | Rigid polyurethane foam | |||||||
Door size (mm) | Single wing: W800 x H1800; Double wing: W1600 x H1800; | |||||||
Note:1. We reserve the right to change specifications without prior notice 2.Customized sizes and configurations available |
3. Feactures:
a. Touch panel for the convenient input of fixed values and programming with graphic depiction of nominal and real values, operating time, remaining cycles etc., including help functions
b. Programme memory for up to 100 programmes with a total of 1000 sections
c. Software support for potential-free inputs and outputs
d. Password protection, two-stage, to avoid unintentional alteration
e. Integrated limit value monitoring system for temperature and humidity
f. Inspection system provides information on malfunctions and collects operating time dat
4. Walk-in Room Internal Show